XSV10-A Cam switch
![XSV10-A](https://www.generi.net/temp/produkt_detail_tmb_137.jpg?v=1676273555)
Explosion-proof control heads type XSV, XMB, XPB a XRP are designed for Ex equipment control (switches, potentiometers – see type key) built in Ex enclosures installed in explosive atmospheres, flammable gases, vapours and dusts, or methane-containing mines.
- Head hole Ø22,5 wall width 1 - 9 mm
- Material: metal
- Lockable handle
- Handle colour: black, red
Type key:
XSV10-A | (1) | (2) | (3) | (4) | (5) |
XSV10-A | Marking | Cam switch |
1 | Control handle |
N - black non-lockable K - black, lockable E - red, lockable |
2 | Positions |
F - fixed |
3 | No. of positions |
2 up to 6 |
4 | Switching code | Determined by manufacturer |
5 | Handle starting position |
A6, B6, C6, D6, V6 |
Example of order code: XSV10-AKF6 D6 (cam switch, black, lockable handle, 6 fixed positions, starting position D6). Specify switching table when ordering. |
Technical data
Basic overview (the head)
- Explosion protection I M2 Ex eb I Mb / II 2G Ex eb IIC Gb / II 2D Ex tb IIIC Db
- Zone 1, 2 and 21, 22 - SNM 1, 2
- Ingress protection IP 67
- Ambient temperature 0°C up to +85°C (I M2), -60°C up to +85°C (II 2G, II 2D)
- Material Cast zinc, zinc galvanized
Basic overview (switching unit)
- Explosion protection II 2G Ec db eb IIC Gb
- Zone 1, 2 and 21, 22 - SNM 1, 2
- Ingress protection IP 20
- Ambient temperature -50°C up to +75°C
- Installation On the head
- Connection Screw terminals for conductor max. 2,5 mm2
Electrical data
- Nominal voltage 415 V
- Rated current 10 A
- Switching capability AC15: 240V / 3A; DC13: 250V / 0,27A
Files to download
Datasheets
![]() |
118 KB | Download | |
![]() |
116 KB | Download |
User manuals
![]()
Explosion-proof control elements
|
476 KB | Download |
Certificates
![]()
Explosion-proof control elements
|
1540 KB | Download | |
![]()
Explosion-proof control elements
|
1687 KB | Download |
Declarations of Conformity
![]()
Explosion-proof control elements
|
85 KB | Download |