Mineral insulated heating cable

Mineral insulated resistance heating cables are preferentially used to maintain high process temperatures, provide high performance and high temperature resistance in applications where thermal limit values for insulation on other cables are exceeded.

These cables come with four types of jackets suitable for different temperatures and applications.

cables are approved for use in normal environments, zones 1, 2 and zones 21, 22.

Mineral insulated cables variants Max. supply voltage (V)
Double-core MI heating cable 300 (Safe/Ex)
Single-core MI heating cable 500
Single-core MI heating cable 800/500 (Safe/Ex)
Longline MI heating cable 750

MIL cable sets are available in different configurations designed according to cable type and number of conductors. The welded cable termination is already carried out in the production.

Note:
1. The voltage depends on the length of the circuit and the design
2. The power output is limited by the maintained temperature.
3. Temperature classes are according to internationally recognized standards of authorized institutions. Heating cables are approved for temperature classes using a stabilized design. This allows the use of cables
     in potentially explosive atmospheres without limiting thermostats. For design of heating circuits contact GENERI, s.r.o.

Single-core, Max. supply voltage: 800/500 V, Temperature resistance : max 600°C
Cable type Conductor resistance (Ohm/m at 20 °C) Cable diameter (mm)
10V2_32 10,00 3,20
6,3V2_32 6,30 3,20
4,0V2_32 4,00 3,20
2,5V2_36 2,50 3,60
1,6V2_38 1,60 3,80
1,0V2_41 1,00 4,10
0,63V2_45 0,63 4,50
0,40V2_50 0,40 5,00
0,25V2_56 0,25 5,60
0,16V2_65 0,16 6,50

For underscore substitute: A - SS 1.4541; L - Alloy 600 (2.4816) - outer sheath material. E.g. 10V2A32

Conductor material : NiCr 8020

If ordering hazardous area version please use "_Ex" at the end, e.g. 10V2A32_Ex 

Single-corer, Max. supply voltage: 500 V, Temperature resistance: max. 400°C
Cable type Conductor resistance (Ohm/m at 20 °C) Cable diameter (mm)
1,6CN2A32 1,60 3,20
1,0CN2A34 1,00 3,40
0,63CN2A37 0,63 3,70
0,40CN2A40 0,40 4,00
0,25CN2A44 0,25 4,40
0,16CN2A49 0,16 4,90

 Outer sheath material: Stainless steel AISI 321 ( 1.4541 )

 Conductor material : CuNi 44


Double-core, Max. supply voltage: 300 V, Temperature resistance : max. 600°C
Cable type Conductor resistance(Ohm/m at 20 °C) Cable diameter (mm)
L2_110-1 36,100 3,6
L2_900-2 29,500 3,7
L2_750-2 24,600 3,7
L2_600-2 19,680 3,7
L2_500-2 16,400 3,7
L2_400-2 13,100 4,1
L2_320-2 10,500 4,1
L2_275-2 9,020 4,1
L2_250-2 8,200 4,3
L2_200-2 6,560 4,6
L2_170-2 5,580 4,1
L2_140-2 4,592 4,3
L2_114-2 3,740 4,3
L2_100-2 3,280 4,3
L2_700-3 2,300 4,6
L2_472-3 1,550 4,3
L2_374-3 1,230 4,3
L2_293-3 0,961 4,3
L2_250-3 0,820 4,3
L2_200-3 0,656 4,1
L2_150-3 0,492 4,1
L2_100-3 0,328 4,6
L2_734-4 0,241 4,6
L2_583-4 0,191 4,3
L2_458-4 0,150 4,3
L2_324-4 0,106 4,3
L2_516-5 0,017 7,1

 For underscore substitute: S -SS 1.4541; H - Alloy 825 (2.4858) - outer sheath material. E.g. L2H110-1

Single-core cable certification : EPS 12 ATEX 1476 X II 2G Ex eb IIC T1...T6
II 2D Ex td IIIC T450°C...T85°C
For information about other certification contact Generi, s.r.o.

 

Double-core cable certification : Sira 10 ATEX 3216 II 2G Ex e IIC T1 to T6 Gb
 
For information about other certification contact Generi, s.r.o.

Technical data

Basic overview

  • Available power output max. 250 W/m
  • Maximum exposure temperature power on 800 °C (power output given by maintained temperature)
  • Maximum exposure temperature power off 1000 °C
  • Minimal bend radius 5x cable diameter
  • Temperature class T1 - T6 (based on stabilized design or with additional temperature limiter)

Electrical data

  • Nominal voltage max. 800 V AC
Files to download

Certificates

ATEX-MIL
ATEX-MIL
pdf 1392 KB Download

Declarations of Conformity

DoC-MIL
DoC-MIL
pdf 475 KB Download

This website uses cookies to ensure you get the best experience on our website.