Intelli Trace - controls and monitoring
Intelli Trace is a control system for monitoring and control of almost unlimited modifications of heating processes. Thanks to the sophisticated system, it is easy to view and adjust the current and required values in operation, not only by local access but also by using the Ethernet module and the Internet network. With the help of the Internet, we are able to analyse the current process condition and, if necessary, to analyse and modify parameters according to the customer's requirements. And all this in bad weather from the warmth of the office, from a computer or a mobile phone with an internet connection. The real advantage is the electricity and cost savings compared to conventional control systems.
Regulation for indirect measurement:
1. Antifreeze SX
Modification for protection against freezing of process media with the use of self-regulating heating cables. Designed for self-regulating heating cables.
2. Progressive SX
Modification for progressive power regulation of the self-regulating heating cable that allows you to reduce power consumption by approx. 25-75%. Designed for self-regulating heating cables. When the ambient temperature drops below set value t1, the system switches to ON and OFF pulse mode, where the time period is 60 seconds and the alternation varies with temperature. When the ambient temperature drops below the set value t2, the system switches to continuous mode ON. When the ambient temperature is raised to t1 + 1 ° C, the system switches to OFF mode.
Regulation example:
t1 = 5°C t2 = -15°C 1°C = 3 seconds (period 60s/regulation range t2 - t1 20°C) |
||
Current ambient temperature (°C) |
ON state (s) |
OFF state (s) |
n to 5 |
0 |
60 |
4,9 to 0 |
3 to 15 |
57 to 45 |
0,1 to 5 |
18 to 30 |
18 to 30 |
-5,1 to -10 |
33 to 45 |
27 to 15 |
-10,1 to -15 |
48 to 60 |
12 to 0 |
-15,1 to -n |
60 |
0 |
3. Progressive const
Suitable for constant wattage heating cables as well as serial and parallel heating cables, provided that the surface temperature of the heating cable (specified by the manufacturer) does not exceed the maximum permitted process temperature of the medium tmax.
Regulation for contact measurements:
1. Set point
Modifications to keep the process temperature of the medium up to the desired value up to 0.1 ° C. Suitable for any type of heating cables.
When entering t1, the system switches to ON when the actual process temperature is lower than the set value t1 -1°C.
When the desired temperature is reached t1 - 1 ° C, the system starts pulsing at 1 second intervals between ON and OFF (to eliminate overshoot).
When the desired temperature t1 is reached, the system switches to OFF.
2. Keep in
Modifications to maintain the process temperature of the medium in the temperature range t1 to t2. Suitable for any type of heating cables.
When entering the required temperature range with t1 and t2, the system switches to ON when the current process temperature of the medium is lower than the set value t1.
When the temperature t1 is reached, the system switches to OFF mode until the current process temperature of the medium drops to a set value of t2-1 ° C, then switches to ON again.