FSE(w) - self-regulating heating cable
Self-regulating heating cables range FSE(w) are primarily designed to maintain process temperature in the pipeline or freeze protection where higher temperature resistance is required.
Power output of the cable FSE(w) is a response to the ambient temperature at any point in the circuit.
Changing the ambient temperature or thermal loss of the insulation is compensated by automatically changing the power at each point of the circuit. This self-regulating feature allows cable crossing without damage due to temperature.
FSE(w) cables are approved for use in normal environments, zones 1, 2 and zones 21, 22.
Terminal boxes for connection of heating cables - are used for powering, connecting and branching of heating cables.
Cable termination
Self-regulating heating cables FSE(w) require the use of a termination set UTK344(555).
Power output curves:
Output power for jacketed cable attached to the insulated metal pipeline at the voltage values listed below:
Type of cable Nominal voltage 230 V AC |
Power output at 10 °C (W/m) |
17FSE | 17 |
31FSE | 31 |
45FSEw | 45 |
60FSEw | 60 |
* CT ... Polyolefin jacket providing additional protection in places where the cable is exposed to the influence of inorganic chemicals based on water basis.
* CF ... Fluoropolymer jacket providing additional protection in places where the cable is exposed to the influence of organic chemicals or corrosive atmospheres..
Certification: FSE - SIRA 02ATEX3076 |
II 2G Ex e IIC T4 Gb |
II 2D Ex tb IIIC T135°C Db IP67 | |
Certification: FSEw - SIRA 12ATEX3114 |
II 2G Ex e IIC T3-T4 Gb |
II 2D Ex tb IIIC T200°C-135°C Db IP67 | |
For information on further certification contact Generi, s.r.o. |
Note:
1. Cables can also be used for other voltages, for information contact Generi staff.
2. Temperature classes are according to internationally recognized standards of authorized institutions.
3. Heating cables are approved for temperature classes using a stabilized design. This allows the use of cables in potentially explosive atmospheres without limiting thermostats. For design
of heating circuits, please contact Generi, s.r.o.
4. For additional accessories for complete installation of the heating cable and for compliance with the approval requirements, refer to the heating cable installation guide.
Size and type of the circuit breaker:
The maximum circuit lengths for the different current values of the circuit breaker are listed below. The size of the circuit breaker and the type of short-circuit protection used must be designed according to national standards. Please contact Generi, s.r.o. for design information and other supply voltages.
Short-circuit protection must be provided for each supply branch of the heating system separately.
Supply voltage 230 V AC | Max. cable length vs. size of the circuit breaker (type C circuit breaker) (m) | |||||
Type of cable | Start-up temperature (°C) | |||||
6A | 10A | 16A | 20A | 25A | ||
17FSE | 10 | 46 | 76 | 120 | 148 | - |
0 | 36 | 62 | 98 | 122 | 148 | |
-20 | 24 | 42 | 66 | 82 | 102 | |
-40 | 16 | 28 | 44 | 56 | 68 | |
31FSE | 10 | 32 | 52 | 82 | 104 | 110 |
0 | 26 | 42 | 68 | 84 | 106 | |
-20 | 16 | 28 | 46 | 56 | 70 | |
-40 | 12 | 18 | 30 | 38 | 48 | |
45FSEw | 10 | 24 | 38 | 62 | 76 | 96 |
0 | 20 | 32 | 50 | 64 | 80 | |
-20 | 12 | 22 | 34 | 42 | 52 | |
-40 | 8 | 14 | 22 | 28 | 34 | |
60FSEw | 10 | 20 | 35 | 52 | 66 | 82 |
0 | 16 | 28 | 44 | 56 | 70 | |
-20 | 12 | 20 | 32 | 40 | 50 | |
-40 | 8 | 14 | 22 | 28 | 34 |
Basic overview
- Maximum exposure temperature power on/ power off 100 °C
- Power output at 10°C 17, 31, 45, 60 W/m
- Nominal voltage 1 - 277 V AC
- Minimum installation temperature - 40 °C
- Minimal bend radius 30 mm
- Temperature class T4 for 17, 31FSE, 45FSEw and T3 for 60FSEw
Datasheets
![]() |
179 KB | Download |
User manuals
![]() |
6534 KB | Download | |
![]() |
5488 KB | Download | |
![]() |
5782 KB | Download | |
![]() |
9353 KB | Download | |
![]() |
4890 KB | Download | |
![]() |
2376 KB | Download | |
![]() |
3203 KB | Download | |
![]() |
1580 KB | Download | |
![]() |
1637 KB | Download |
Certificates
![]() |
183 KB | Download | |
![]() |
191 KB | Download | |
![]() |
5076 KB | Download |
Declarations of Conformity
![]() |
415 KB | Download | |
![]() |
223 KB | Download |