Electronic switches – range GES

The electronic range switches GES10 are designed for DIN rail applications in control systems functioning as thermostats or other two-state regulators. Their output signal (switched on or off) is dependent on the instantaneous value of the measured value and the comparator value set on the switch. In this sense, when switching to the set value, the galvanically isolated relay contacts are switched. The main components of the switch are an electronic comparator with adjustable element, a hysteresis regulating module and an output relay with switching contacts for 250 VAC and load current of 8 A. The switches are equipped with a heating-cooling mode switch enabling a change of the output contacts characteristics, which predisposes them to control the refrigeration aggregates and ventilation, as well as two-stage regulation of heating systems. In terms of supply voltage, the switches are manufactured in versions for 230 V / 50 Hz, for 24 V / 50 Hz or 24 V DC.

Input / supply 230 V/50Hz 24 V/50Hz 24 V DC
Ni1000/5000 ppm GES10L/230 GES10L/24AC GES10L/24DC
Ni1000/6180 ppm GES10S/230 GES10S/24AC GES10S/24DC
Pt100 GES10P/230 GES10P/24AC GES10P/24DC
4 up to 20 mA GES10I/230 GES10I/24AC GES10I/24DC
0 up to 10 V GES10U/230 GES10U/24AC GES10U/24DC

Basic technical parameters

Standard regulation range - 25 up to 15 °C, 10 up to 34 °C
0 up to 40 °C, 40 up to 80 °C
20 up to 60 °C, 40 up to 120 °C
0 up to 80 °C, 80 up to 120 °C
Input range/except temperature/ customer specified
Supply voltage GESxx/230
GESxx/24AC
GESxx/24DC
230 V/50Hz 0,5 VA
24 V/50Hz +-10% 0,5 VA
24 V DC +-20% 0,5 W
Max. switching voltage 250 V AC
Max. switching capacity 8 A change-over contact
Hysteresis adjustable 1 - 5 °C or 2 - 10% (Type I, U)
 Protection  IP 40
 Terminals protection  IP 20
 Ambient temperature - working  - 25 up to 60 °C
 Ambient temperature - storage  - 25 up to 80 °C
 Relative humidity  < 70%
 Connection  Terminal CLL 5/2, conductor cross-section max. 2,5mm2

These thermostats have the character of permanently connected devices and therefore the operator must ensure that a switch or circuit breaker is marked as a device disconnector in their immediate vicinity. This must be easily reachable by the operator.

Installation and commissioning
Installation, start-up or commissioning may only be carried out by a person qualified in accordance with local laws.
The switch is mounted using the TS35 DIN rail holder. Connect the input signal to terminals 3 and 2 or 1 and the supply voltage to L, N terminals(or + and - for 24 V DC). The output signal of the control relay is wired to A, B, C terminals. It is recommended to use supply cables with a cross section from 0.35 to 2.5 mm2.

Dimensions and accessories
Contact relays are displayed it theirs stand-by position corresponding with supply voltage disconnection.

Mode „Heating”: - JUMPER in O position - if the measured value is lower than desired value, the contacts A, C are closed.

Mode „Cooling”: - JUMPER in CH position - if the measured value is higher than the desired value, the contacts A, C are closed.

Dimensional drawing

Ordering information
When ordering, please state type and amount, e.g.:
5 pcs of electronic switch GES10L/230, regulation range 0 - 80 °C